Installing and Maintaining BN Platforms
1-6 109352-E Rev. A
Space Requirements
Make sure the installation site is large enough for the BLN and provides sufficient
air plenum (a volume of free space surrounding the hardware platform for heat
exhaust). Table 1-4 lists the dimensions of the BLN.
Table 1-5 lists the number of British thermal units (Btus) generated by the BLN
and its air plenum requirements.
Table 1-6 lists the total space needed (dimensions plus air plenum requirements)
for the BLN.
Table 1-4. BLN Dimensions
Height Depth Width
14 in. (35.6 cm) 29.9 in. (58.2 cm) 17.3 in. (44 cm)
Table 1-5. BLN Thermal Output and Air Plenum Requirements
Thermal Output
(Maximum Btu/hr) Location of Air Plenum
Minimum Required Air
Plenum
2600 Right 2 in. (5.1 cm)
Left 2 in. (5.1 cm)
Front 1 in. (2.5 cm)
Table 1-6. Total Space Required for BLN
Height Depth Width
8.75 in. (22.2 cm) 19.5 in. (49.5 cm) 21.3 in. (54.1 cm)